- Gloves (Class 00 through Class 4)
- Sleeves
- Blankets
- Hot Sticks
- Line Hose
- Personal Protective Grounds
- Bucket Liners
| Class |
AC Proof Test Voltage |
DC Proof Test Voltage |
Maximum Use Voltage |
| 00 |
2,500 |
10,000 |
500 |
| 0 |
5,000 |
20,000 |
1,000 |
| 1 |
10,000 |
40,000 |
7,500 |
| 2 |
20,000 |
50,000 |
17,000 |
| 3 |
30,000 |
60,000 |
26,500 |
| 4 |
40,000 |
70,000 |
36,000 |
- Equipment is checked in and a tracking number assigned.
- All equipment is thoroughly cleaned and dried.
- Visual inspection follows.
- Once clean the equipment is dielectrically tested.
- Visual inspection follows and if passed it is stamped with tested date.
- Any equipment that fails either test is stamped "rejected" and is either returned or destroyed, per your request.
- Tracking logs are provided for all of your equipment as well as test history kept on file.
|